Skip to main content
Electricity & EnergyFree · no sign-up

Power Factor Calculator

Power factor and reactive power from real watts and apparent VA — the power triangle.

Updated

800 W
1,000 VA

You need

0.80power factor

800 W of 1,000 VA does real work

Power factor
0.80
Reactive power
600 VAR

Advertisement

In short

What is a power factor of 0.8?

Power factor = real power in watts ÷ apparent power in volt-amps, so a load drawing 800 W from a 1,000 VA supply has a power factor of 0.80. The rest is reactive power: the square root of 1,000 squared minus 800 squared is 600 VAR, swinging back and forth each cycle doing no work at all.

A low power factor is normal on motors and correctable with capacitors, but on something that should be resistive it usually means one of your two measurements is wrong.

How to use the power factor calculator

Enter the real power in watts and the apparent power in volt-amps and the tool returns the power factor, a number between 0 and 1, along with the reactive power in VAR. Power factor is simply the ratio of the two: the watts that do actual work divided by the volt-amps the supply has to deliver to get that work done.

A device rated 800 W that draws 1,000 VA has a power factor of 0.80, which means four-fifths of what the circuit carries turns into useful output and the remaining fifth is current flowing back and forth without producing anything. Keep both inputs in the same units, because entering watts alongside kilovolt-amps produces an answer that is wrong by a factor of a thousand.

0.80

Power factor

800 W of real work from 1,000 VA

600 VAR

Reactive power

swinging back and forth, doing nothing

cos φ

The same ratio, as an angle

the cosine of the phase shift

The two numbers come off the equipment in different ways, and knowing which is which prevents most bad results. Real power in watts is the figure on an energy label or read from a wattmeter, and it accounts for the phase relationship between voltage and current internally. Apparent power in volt-amps is what you get from an ordinary clamp meter and a voltmeter: measured amps multiplied by measured volts, with no phase correction at all.

Getting volt-amps from a clamp meter

Apparent power is measured amps multiplied by measured volts. The amps to watts calculator does that multiplication at 120 V or 240 V when a clamp reading is all you have.

Open the amps to watts calculator

Advertisement

The gap between them is the reactive power, and the smaller that gap, the closer the power factor sits to 1.0. You would reach for this tool to put a number on a motor, a whole distribution panel, or a piece of equipment whose nameplate quotes VA when you wanted watts.

Power factor matters most on a commercial or industrial account, where the utility can charge for it. Large inductive loads such as motors, transformers and magnetic ballasts draw a magnetising current that swings out and back each cycle without doing work, and that current still has to be carried by every conductor and every transformer between the generator and the plant floor.

Utilities therefore meter power factor on larger accounts and apply a penalty when it falls too low. Thresholds and methods vary by tariff, but industry references describe utilities commonly starting to penalise somewhere in the 0.85 to 0.95 range, usually either by billing on kVA demand rather than kW demand or by multiplying the demand charge by a ratio of target power factor to actual.

For a home this is mostly background knowledge rather than a bill you can lower. Residential meters bill real kilowatt-hours, so a poor power factor on a household appliance does not normally cost you anything directly the way it does a factory. It is still worth understanding in two situations: reading a motor nameplate, and sizing a generator or a UPS.

Both of those are rated in volt-amps rather than watts precisely because they have to supply the apparent power, not just the real power, so a 1,000 VA UPS will not carry a 1,000 W load with a poor power factor. Read the result as a snapshot of how hard the supply is working relative to what it achieves, and leave correction equipment on a real installation to a licensed electrician.

Do

  • Take the real power in watts from a wattmeter, energy label or motor nameplate.
  • Keep both inputs in the same units, either base units or thousands.
  • Check the result against a typical value for that class of equipment.
  • Size a generator or a UPS on volt-amps rather than on watts.

Don't

  • Mix watts with kilovolt-amps, which lands the answer off by a thousand.
  • Expect a household bill to fall, since residential meters bill real kilowatt-hours.
  • Size correction capacitors from a single reading on this page.
  • Assume a low reading on a resistive load is real rather than a measurement error.

Typical power factors by load type, each translated into what it costs the supply. The third and fourth columns hold real power fixed at 1,000 W and show what the circuit has to carry to deliver it, which is the honest way to see the penalty: a lightly loaded motor asks the supply for up to three times the volt-amps that an equivalent heater does for identical useful output.

Load typeTypical power factorApparent power for 1,000 W of real powerReactive power carried
Incandescent lamp, resistance heater, electric kettle1.001,000 VA0 VAR
Electric oven element or resistive water heater1.001,000 VA0 VAR
LED lamp with a good driver0.90 to 0.991,010 to 1,111 VA142 to 484 VAR
Fluorescent lighting, electronic ballast0.90 to 0.951,053 to 1,111 VA329 to 484 VAR
Small adjustable-speed drive0.90 to 0.981,020 to 1,111 VA203 to 484 VAR
Squirrel-cage induction motor, 5 to 300 hp, at full load0.84 to 0.911,099 to 1,190 VA456 to 646 VAR
Induction motor at full load, general range0.80 to 0.901,111 to 1,250 VA484 to 750 VAR
Fluorescent lighting, magnetic ballast0.70 to 0.801,250 to 1,429 VA750 to 1,020 VAR
Mixed industrial load, uncorrected0.70 to 0.851,176 to 1,429 VA620 to 1,020 VAR
Induction motor running lightly loaded0.30 to 0.601,667 to 3,333 VA1,333 to 3,180 VAR
Arc welder0.35 to 0.801,250 to 2,857 VA750 to 2,676 VAR
Transformer energised at very light load0.20 to 0.502,000 to 5,000 VA1,732 to 4,899 VAR
Typical utility penalty threshold on a commercial account0.85 to 0.951,053 to 1,176 VA329 to 620 VAR
Plant after capacitor correction0.95 to 1.001,000 to 1,053 VA0 to 329 VAR
Compiled July 2026. Power factor ranges are typical published values from utility and engineering power-factor references and vary by make, load level and design, so measure your own equipment rather than sizing from this table. Apparent power and reactive power are computed here from each power factor for a fixed 1,000 W of real power, using VA = W ÷ PF and VAR = the square root of VA squared minus W squared.

What a poor power factor costs in supply capacity

Run the arithmetic backwards to see what a poor power factor costs in supply capacity. Holding real power at 1,000 W, a power factor of 1.00 needs 1,000 VA and no reactive power. At 0.80 the supply must carry 1,250 VA and 750 VAR.

At 0.50, which a lightly loaded motor or an idling transformer can reach, it must carry 2,000 VA and 1,732 VAR, so twice the current for the same useful output. Every conductor, breaker, transformer and generator in the path has to be rated for that larger figure, which is why apparent power is what equipment ratings are written in.

Apparent power the supply must carry for 1,000 W of real work(volt-amps)
Power factor 1.001,000 VA
Power factor 0.801,250 VA
Power factor 0.502,000 VA

Read it: The useful output never changes down this chart; only the current carried alongside it does, and at 0.50 the supply is working twice as hard as the load ever notices.

Computed from VA = W ÷ PF at a fixed 1,000 W, the same relationship the tool uses.

Advertisement

The formula, worked line by line

On an alternating-current circuit, voltage and current are not necessarily in step. Where they are, every instant of current is doing work and the watts equal the volt-amps. Where an inductive load pushes the current out of phase with the voltage, part of each cycle sees energy flowing into the load and part sees it flowing back out again, so the supply carries current that never becomes useful output. Power factor is the fraction that does.

The three quantities form a right triangle, which is where the square root comes from. Real power in watts is one leg, reactive power in VAR is the other, and apparent power in volt-amps is the hypotenuse. That geometry means reactive power is always recoverable from the other two, and it also means power factor equals the cosine of the phase angle between voltage and current, which is why it is often written as cos phi.

power factor = real power (W) ÷ apparent power (VA)
reactive power (VAR) = √(VA² − W²)
apparent power (VA) = real power (W) ÷ power factor
800 ÷ 1,000 = 0.80;  √(1,000² − 800²) = 600 VAR
The power triangle800 watts of real power and 1,000 VA of apparent power give a power factor of 0.80, with 600 VAR of reactive power as the third side of the right triangle.REAL / REACTIVE / APPARENTreal 800 W600 VARapparent 1,000 VApower factor0.80
800 W real and 1,000 VA apparent make a 0.80 power factor — 600 VAR reactive.
The worked default, as a triangle
Real power
800 W
Apparent power
1,000 VA
Power factor
800 ÷ 1,000 = 0.80
Reactive power
√(1,000² − 800²) = 600 VAR

The reactive power is the square root of 1,000,000 minus 640,000, which is the square root of 360,000. So of the 1,000 volt-amps the supply delivers, 800 do real work and 600 swing back and forth each cycle achieving nothing. Those three numbers form a right triangle with legs of 800 and 600 and a hypotenuse of 1,000, the familiar 3-4-5 proportions scaled by 200.

That reactive current is exactly what utilities charge for on larger accounts. Practice varies by tariff, but references describe penalties commonly starting somewhere between 0.85 and 0.95, applied either by billing on kVA demand instead of kW demand or by scaling the demand charge by the ratio of a target power factor to the measured one.

Residential meters bill real kilowatt-hours, so households rarely see it, and the value of the number at home is in reading motor nameplates and sizing generator or UPS capacity honestly rather than in lowering any bill.

Advertisement

Questions people ask

What does a power factor of 0.8 mean?

It means only 80 percent of the apparent power the supply delivers is doing real work. A load rated 800 W drawing 1,000 VA sits at 0.80, and the square root of 1,000 squared minus 800 squared gives 600 VAR of reactive power that swings back and forth each cycle without producing anything. It is an entirely typical figure for motors and other inductive loads, and on a commercial account it sits at or below the range where utilities commonly begin applying a low power factor penalty.

Covered in depth in What Is Power Factor? The Current Your Watts Do Not Show

Does power factor affect my home electricity bill?

Rarely in any direct way. Residential meters bill real watts, which are the kilowatt-hours printed on your statement, so a poor power factor on a household appliance does not usually cost you anything extra. Power factor penalties are a feature of commercial and industrial tariffs, where the utility meters it separately on larger accounts. At home the value of understanding it is elsewhere: reading a motor nameplate correctly, and sizing a generator or a UPS, both of which are rated in volt-amps rather than watts.

What is the difference between real power and apparent power?

Real power, in watts, is the part that actually does something: heating, spinning, lighting. Apparent power, in volt-amps, is the total the supply must deliver, measured volts multiplied by measured amps with no correction for phase. On a purely resistive load the two are equal. On an inductive load current lags voltage and they diverge, with reactive power in VAR as the third side of the right triangle joining them. Power factor is real divided by apparent, and equals the cosine of the phase angle between voltage and current.

What causes a low power factor?

Inductive loads, overwhelmingly. Motors, transformers and magnetic fluorescent ballasts draw a magnetising current that flows out and back each cycle without doing work, pulling the power factor below 1.0. Motors are the usual culprit on an industrial floor, and a motor running lightly loaded is far worse than the same motor at full load, since the magnetising current stays roughly constant while the useful output falls away. Purely resistive loads such as heaters and incandescent lamps sit at or extremely close to 1.0.

What is reactive power measured in VAR?

Reactive power, in volt-amperes reactive, is the portion of the supply capacity that is borrowed and returned each cycle without doing useful work. It is the third side of the power triangle: real power and reactive power are the two legs and apparent power is the hypotenuse, so reactive power equals the square root of VA squared minus W squared. With the defaults that is the square root of 360,000, or 600 VAR. It performs no work, but every conductor in the path still has to carry the current it represents.

Sources

Where the constants and formulas on this page come from. Each line names the figure it backs.

  1. That utilities bill low power factor through kVA demand or a target-to-actual ratio, and that problems start below about 0.95.

    Reducing Power Factor Cost (Motor Systems Tip Sheet)US Department of Energy

Shop clamp multimeters on Amazon

Browse current options and prices directly on Amazon — we don’t list products here.

As an Amazon Associate we may earn from qualifying purchases.