Skip to main content
Electricity & EnergyFree · no sign-up

Solar Battery Bank Size Calculator

Size an off-grid or backup battery bank — usage, days of autonomy, voltage, and usable depth.

Updated

10 kWh/day
1 day
80%

You need

260 Ahat 48 V

12.5 kWh of usable storage

Bank capacity
12,500 Wh
Energy to cover
10,000 Wh

Advertisement

In short

How many amp-hours do I need for 10 kWh a day?

Bank Ah = daily kWh × 1,000 × days of autonomy ÷ depth of discharge ÷ system voltage. For 10 kWh a day with one day of autonomy at 80 percent usable, that is 12,500 Wh of bank capacity, which comes to about 260 Ah at 48 V, 521 Ah at 24 V, or 1,042 Ah at 12 V for exactly the same stored energy.

Sizing a bank on paper is not the same as designing an installation, and battery systems wired into a building or vehicle need a licensed electrician or installer.

How to use the solar battery bank size calculator

Enter the daily electricity the bank has to supply in kilowatt-hours, the days of autonomy you want, the system voltage the bank runs at, and the usable depth of discharge, and the tool returns the bank size in amp-hours plus the same capacity expressed in watt-hours and kilowatt-hours. Amp-hours leads because that is how batteries are sold, labelled and wired together.

The watt-hour figure is the one to trust when comparing options, because it is independent of system voltage and therefore the only fair basis for judging two different bank architectures against each other. Both numbers describe gross nameplate capacity, already scaled up so that the slice you actually use covers your energy need.

12,500 Wh

Gross bank capacity

10 kWh a day, one day, 80 percent usable

260 Ah

At 48 V

how that bank is bought and wired

1,042 Ah

At 12 V

the same energy, four times the amp-hours

Start with the daily usage, and be careful about which loads you count. This is the energy the battery must carry, not the energy your solar array produces and not necessarily your whole household consumption. For a grid-tied backup you might only be sizing for a fridge, a furnace fan, a well pump and some lighting, which could be two or three kilowatt-hours a day.

Advertisement

For a full off-grid cabin it is everything, which is where figures around 10 kWh a day come from. If you do not have a number yet, add up each load wattage multiplied by the hours it runs, then divide by 1,000.

Checking one specific battery instead?

The battery watt-hours calculator handles the reverse direction when you want to check what a specific battery holds.

Open the battery watt-hours calculator

Days of autonomy is the input people underestimate, and it is a straight multiplier on the answer. It is how long the bank must carry the loads with no meaningful charge arriving: a run of overcast days when the array barely produces, or a grid outage you have to ride out entirely on stored energy.

One day is the common default for grid-tied backup where an outage is measured in hours. Off-grid systems in cloudier climates are frequently sized for two or three, because a single genuinely dark stretch can otherwise empty the bank and leave you with nothing. Every extra day multiplies the bank proportionally, so moving from one day to three triples both the cost and the physical space the batteries occupy.

Do

  • Count only the loads that run off the battery, not your whole household usage.
  • Match the depth of discharge to the chemistry you actually intend to buy.
  • Compare two banks on watt-hours, the figure that does not shift with system voltage.
  • Size for two or three days of autonomy where dark stretches are normal.
  • Have a licensed electrician or installer sign off anything permanently wired in.

Don't

  • Assume the daily solar production and the daily battery load are the same figure.
  • Size a lead-acid bank at the 80 percent depth lithium is designed for.
  • Read the amp-hour result as usable capacity; it is gross nameplate capacity.
  • Expect the rated capacity in the cold or under a fast discharge.
  • Take this for an array size, since it sizes storage only.

A ready-reckoner for bank sizing at 80 percent usable depth of discharge, covering everything from a weekend van fit-out to a large off-grid home. The three amp-hour columns are the same stored energy counted at three different system voltages, which makes the case for 48 V more vividly than any argument does: look at what happens to the 12 V column by the bottom of the table.

Daily useDays of autonomyBank capacity at 80 percent usableAmp-hours at 48 VAmp-hours at 24 VAmp-hours at 12 V
1 kWh (a van fridge and lighting)1 day1.25 kWh26 Ah52 Ah104 Ah
2 kWh1 day2.5 kWh52 Ah104 Ah208 Ah
3 kWh (essentials-only outage backup)1 day3.75 kWh78 Ah156 Ah313 Ah
5 kWh (small cabin)1 day6.25 kWh130 Ah260 Ah521 Ah
5 kWh2 days12.5 kWh260 Ah521 Ah1,042 Ah
8 kWh1 day10 kWh208 Ah417 Ah833 Ah
10 kWh (the tool default)1 day12.5 kWh260 Ah521 Ah1,042 Ah
10 kWh2 days25 kWh521 Ah1,042 Ah2,083 Ah
10 kWh3 days37.5 kWh781 Ah1,563 Ah3,125 Ah
15 kWh1 day18.75 kWh391 Ah781 Ah1,563 Ah
15 kWh2 days37.5 kWh781 Ah1,563 Ah3,125 Ah
20 kWh (a fully electric off-grid home)1 day25 kWh521 Ah1,042 Ah2,083 Ah
20 kWh2 days50 kWh1,042 Ah2,083 Ah4,167 Ah
30 kWh1 day37.5 kWh781 Ah1,563 Ah3,125 Ah
Computed July 2026 using the same arithmetic as the tool, at an 80 percent usable depth of discharge throughout. For a lead-acid bank at 50 percent usable, multiply every capacity and amp-hour figure in the table by 1.6. Amp-hours are gross nameplate capacity, not usable capacity, and real installations also need allowance for charge efficiency, temperature and cable losses.

How much do chemistry and bus voltage change the bank?

Depth of discharge is the other big lever and it is set entirely by chemistry. Lead-acid banks are conventionally sized around 50 percent usable, and Trojan recommends discharging its deep-cycle batteries only 20 to 50 percent of rated capacity for optimum life. LiFePO4 is designed for far deeper cycling, with Battle Born rating its packs for 100 percent usable depth of discharge and a cycle life of 3,000 to 5,000.

Because you divide by that fraction, the same energy need produces a bank roughly 1.6 times larger on lead-acid than on lithium. System voltage, meanwhile, changes only the amp-hours and not the energy: a 48 V bank holds the same watt-hours as a 12 V one using a quarter of the amp-hours, which is why larger systems run at 48 V and move the same power at lower current.

The same 12,500 Wh bank, counted at three bus voltages(amp-hours of nameplate capacity)
12 V1,042 Ah
24 V521 Ah
48 V260 Ah

Read it: Identical stored energy in every row; the higher bus simply moves the same power at a quarter of the current, which is why cables, fuses and busbars all shrink at 48 V.

Computed as bank Wh ÷ system voltage, the same arithmetic as the tool.

Advertisement

The formula, worked line by line

The bank has to hold a day of energy multiplied by your days of autonomy, then be scaled up so that the fraction you are willing to use covers that need, then converted into amp-hours at whatever voltage the bank runs. Daily kilowatt-hours are multiplied by 1,000 first, so the units line up with the volts and amp-hours batteries are actually rated in rather than the kilowatt-hours your bills are.

Two of the three terms are straight multipliers and behave predictably: double the autonomy and the bank doubles, halve the depth of discharge and the bank doubles again. The voltage term is different in character because it changes only how the same energy is counted. Watt-hours stay put while amp-hours scale inversely with voltage, which is the entire reason large systems move to 48 V.

needed Wh = daily kWh × 1000 × days of autonomy
bank Wh = needed Wh ÷ usable depth of discharge
bank Ah = bank Wh ÷ system voltage
10 × 1000 × 1 ÷ 0.80 ÷ 48 = 260 Ah
Sizing a battery bank10 kWh a day for 1 day is 10,000 watt-hours; divided by 80 percent usable is 12,500 watt-hours, which at 48 volts is about 260 amp-hours.USAGE × AUTONOMY ÷ DoDenergy needed10,000 Wh÷ 80% usable12,500 Wh÷ 48 Vbattery bank260 Ah
10 kWh for 1 day at 80% usable is 12,500 Wh — about 260 Ah at 48 V.
The worked default, term by term
Daily energy
10 kWh × 1,000 = 10,000 Wh
Days of autonomy
× 1
Usable depth of discharge
÷ 0.80 = 12,500 Wh gross
System voltage
÷ 48 V
Bank size
260.4 Ah

The division by 0.80 exists because you only intend to draw four-fifths of the bank, so a 48 V bank of roughly 260 Ah covers one cloudy day of a 10 kWh load. The same 12,500 Wh is 520.8 Ah at 24 V and 1,041.7 Ah at 12 V.

Move each lever separately to see its weight. Going from one day of autonomy to two doubles the bank; switching from 80 percent lithium to 50 percent lead-acid raises it by 60 percent for identical delivered energy; doing both at once compounds them.

The 10 kWh daily load, three ways to grow the bank
Two days of autonomy, lithium
25 kWh · about 521 Ah at 48 V
One day, lead-acid at 50 percent
20,000 Wh · about 417 Ah at 48 V
Three days of autonomy on lead-acid
60,000 Wh · 1,250 Ah at 48 V

Every row starts from the same worked default of 12,500 Wh and about 260 Ah at 48 V; the levers alone do the growing.

Advertisement

Questions people ask

How many amp-hours do I need for 10 kWh a day?

For one day of autonomy at 80 percent usable depth of discharge, 10 kWh of daily use needs 12,500 Wh of gross bank capacity, which is about 260 Ah at 48 V, 521 Ah at 24 V, or 1,042 Ah at 12 V. Those three figures are the same stored energy counted at three different voltages, not three different bank sizes. Ask for two cloudy days of cover instead of one and every one of them doubles, and switching to lead-acid at 50 percent usable raises them by a further 60 percent.

Covered in depth in What Size Solar System Do I Need to Go Off Grid?

What does days of autonomy actually mean?

It is how many days the bank must power your loads on its own with no meaningful charge arriving: an overcast stretch when the array barely produces, or a grid outage you have to ride out entirely on stored energy. One day is the usual default for grid-tied backup, where outages are measured in hours. Off-grid systems in cloudier climates are often sized for two or three days, because a single genuinely dark run can otherwise empty the bank. Each extra day multiplies the bank proportionally, in cost and in physical space.

How much does lead-acid versus lithium change the bank size?

Substantially, because you size around the usable slice rather than the nameplate. Lead-acid banks are conventionally designed at 50 percent usable, and Trojan recommends discharging its deep-cycle batteries only 20 to 50 percent of rated capacity for optimum life. LiFePO4 is designed for 80 percent, with Battle Born publishing 3,000 to 5,000 cycles at that depth. So a 10,000 Wh energy need becomes 20,000 Wh of lead-acid bank but only 12,500 Wh of lithium. Lead-acid costs less per kilowatt-hour but you have to buy and house about 60 percent more of it.

Why does a 48 V bank need fewer amp-hours than a 12 V one?

Because amp-hours only describe charge, and energy is charge multiplied by voltage. The same 12,500 Wh is about 260 Ah at 48 V but 1,042 Ah at 12 V, four times the amp-hours for identical stored energy. The practical consequence is current: a higher voltage moves the same power at a quarter of the amps, so cables, fuses and busbars can all be smaller and voltage drop along them is far less punishing. That is why larger off-grid systems are built at 48 V almost as a matter of course.

Does this size my solar array as well as the battery?

No, this sizes the storage only, which is the part that carries you through nights and cloudy spells. How much generation you need to refill that bank each day is a separate question the solar panel output calculator answers from your system size, peak sun hours and losses. Use the two together: this tool sets the storage, that one sets the production, and the battery watt-hours calculator checks what any individual battery on your shortlist actually holds. A licensed installer should size and sign off the finished system.

Sources

Where the constants and formulas on this page come from. Each line names the figure it backs.

  1. That Trojan recommends discharging its deep-cycle batteries only 20 to 50 percent of rated capacity for optimum life, which is why lead-acid banks here are sized around 50 percent usable.

    Frequently Asked QuestionsTrojan Battery Company

  2. The published cycle life of 3,000 to 5,000 and the 100 percent usable depth of discharge quoted for LiFePO4.

    12V 100Ah LiFePO4 Deep Cycle Battery — specificationsBattle Born Batteries, August 2026

Shop solar panel kits on Amazon

Browse current options and prices directly on Amazon — we don’t list products here.

As an Amazon Associate we may earn from qualifying purchases.